9. Appendix - Replacing an LP-1 With an LP-2/3
Please consider the following differences:
Item LP-1 LP-2/3
Power Wiring
SOL
DC/BAT
12V OUT
SOLAR +
SOLAR -
DC INPUT
OV
12V OUT
OV
+
-
+
-
+
-
+B
GND
24V
+BAT
+VDC IN
GND / 0 V
GND / 0 V
24V OUT
+VDC1 OUT
+VIN
GND
+V1
POWER
Analog Wiring
12/24
V
5V AUX 0V
ANALOG INPUTS
4+
3+ 2+ 1+
12V AUX
AI CH 1
AI CH 4
AI CH 2
AI CH 3
0V
5V OUT
GND
AO VOLTAGE
AI CH 1
AI CH 4
AI CH 2
AI CH 3
GND / 0V
AO CURRENT
AOV
AOC
ANALOG OUT
ANALOG INPUTS
AI4
AI3
AI2
AI1
#DI1.9 0 [default] = port 3 disabled Always 0 (no longer used)
#DI1.10 0 [default] = port 4 disabled 1 = port 3 or port 4 detected
#DO2.11
0 [default] = disable 12V Out 1 [default] = enable V1 Out
#DO2.13 1 [default] = disable port 3
1 [default] = enable 24V Out
#DO2.14 1 [default] = disable port 4 0 [default] = enable ports 3 and 4
#AI1.8
Supply Voltage 0 to 32760 = 0 to 25 V Supply Voltage 0 to 32760 = 0 to 20.15 V
#AI2.7 Trio SR radio TX power Port 3 option board type
#AO2.9
0 [default] = shutdown at 10.4 V and
check supply every 5 minutes
38 Hex [default] = disable low voltage
shutdown
NOTES:
• LP-1 configurations that use port 3 (Trio analog radio or internal GSM) typically clear #DO2.13 (port 3
disable) when ladder logic is first scanned. Clearing #DO2.13 in an LP-2/3 will disable 24V Out.
• If using a backup battery, ensure #AO2.9 is set to 256 (100 Hex) in ladder logic to enable low voltage
shutdown and checking of the supply every minute.
To check if any of the above registers are used in ladder
logic, view the logic using Toolbox 32. Then select
Ladder, Find (or press CTRL+F). Enter each of the
above registers in the Search for parameter or label
field as shown.