User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
20
Communications Ports
1 (fixed)
2 (fixed)
3 (optional)
4 (optional)
(
Supported by
LP-3 only)
Port 1
RS232C 300 to 38400 bps Non-isolated
Data format 8 data bits, no parity, 1 stop (8, N, 1)
Isolation None
Port 2
RS232C/RS422/RS485 300 to 38400 bps Isolated
Output Power +4.3 V @ 100 mA
RS422 Line drive 10 Receivers
RS485 Line drive 32 Receivers
Data format 8 data bits, no parity, 1 stop (8, N, 1)
Isolation 2.5 kV
Port 3
Port 4
Option boards supported: Isolated Serial
(RS232/RS422/RS485 300 to 115200 bps), PSTN (33.6
kbps), Line-2 2/4 Wire Leased Line or Analog Radio*,
Fibre Optic and Spread Spectrum Radio.
Ethernet, HART and Image Capture option boards are
NOT supported.
Full specifications are detailed in the Kingfisher PLUS+
Hardware manual (available from www.cse-
semaphore.com/mykingfisher).
*Note: When an external radio is used with the Line-2
option board, the carrier detect (CD) input on the RJ45 is
not used. Carrier detect is based on detection of tones.
RJ45
Pin
Port 1 or Port 2
RS232C
Port 2
RS422 / RS485
*
RJ45 Socket
RJ45 Plug
87654321
12345678
GR
EEN
/
WH
ITE
1
GREEN
2
ORANGE
/
WH
ITE
3
BLUE
4
BLUE
/
WH
ITE
5
ORANGE
6
BROWN / WH
ITE
7
BROWN
8
1 DTR N/A
2 4.3 V N/A
3 RTS TX+
4 DCD N/A
5 GND (0 V) GND
6 CTS RX+
7 RXD RX-
8 TXD TX-
*
Wire TX- and RX- together to obtain LINE- (RS485). Wire TX+ and RX+ together to obtain LINE+ (RS485).