Hardware Setup Registers
Register
Description Default
Comments Read/Write
DI1.10 Port 3 or Port 4 detected - 1 = one or two option ports detected Read
DO1.13 Pulse input 1 enable 1 1 = enabled. Also allows wakeup via DI1 Read/Write
DO1.14 Pulse input 2 enable 1 1 = enabled. Also allows wakeup via DI2 Read/Write
DO1.15 Pulse input 1 active transition
0 0 = low to high transition, 1 = high to low Read/Write
DO1.16 Pulse input 2 active transition
0 0 = low to high transition, 1 = high to low Read/Write
DO2.7 DO3 enable 0 0 = DO3 disabled & DI5 enabled Read/Write
DO2.8 DO4 enable 0 0 = DO4 disabled & DI6 enabled Read/Write
DO2.9 DO5 enable 0 0 = DO5 disabled & DI7 enabled Read/Write
DO2.10 DO6 enable 0 0 = DO6 disabled & DI8 enabled Read/Write
DO2.11
V1 Out enable
1
1 = V1 Out enabled
Read/Write
DO2.12
I/O & 5V Out disable
0
0 = I/O and 5V Out enabled
When disabled (1 or ON):
• Switches off 5V Out
• Stops updating analog inputs and
digital inputs 3 to 8
• Analog output is set to 0 (LP-3 only)
• Digital inputs 1 & 2 and Digital
outputs 1& 2 still operate
• Disables power to ports 3 and 4
Note 1: I/O & 5V Out must be enabled for
low voltage shutdown to operate correctly
(allows reading of supply voltage)
Note 2: CPU 5V Out remains enabled
Read/Write
DO2.13
24V Out enable
1
1 =24V Out enabled
Read/Write
DO2.14 Port 3 and Port 4 disable 0 0 = Port 3 and Port 4 enabled Read/Write
AO5.5 Pulse Output count 0 Uses DO Ch3 (must be enabled) Read/Write
AO5.6 Pulse ON time 0 x 1ms Read/Write
AO5.7 Pulse OFF time 0 x 1ms Read/Write
DO6.1 Analog input 1 live zero 0 0=0-5 V or 0-20 mA, 1=1-5 V or 4-20 mA*
Read/Write
DO6.2 Analog input 2 live zero 0 0=0-5 V or 0-20 mA, 1=1-5 V or 4-20 mA*
Read/Write
DO6.3 Analog input 3 live zero 0 0=0-5 V or 0-20 mA, 1=1-5 V or 4-20 mA*
Read/Write
DO6.4 Analog input 4 live zero 0 0=0-5 V or 0-20 mA, 1=1-5 V or 4-20 mA*
Read/Write
AO3.9,
AO3.10
Pulse 1 (DI1) or pulse 2 (DI2)
debounce time respectively
0 0 to 32000 ms debounce time
The pulse must remain in the active state
for the debounce time before a pulse is
counted
(0 = no debounce)
Read/Write
AO4.2,
AO4.3,
AO4.4,
AO4.5
Analog input 1 to 4 average
sample count respectively
1 1-59 samples. Number of samples to
average the analog input over before
updating the analog input data register.
Each sample takes up to 110 ms.
Read/Write
* Analog inputs can be changed from voltage to current inputs by installing an external 250 Ω resistor.