User manual

Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
6
6.
Configure the following settings from
the Configuration menu:
Address & DescriptionSet Site
Address to a number in the range of 1
to 249
System Parameters – Set RTU/CPU
Type to LP-1/2/3
Memory – Set Event Logs to 64K,
Compiled Logic to 32K, Network Reg
Blocks to 2K and Firmware Drivers to
32K (other values can be used). Note:
up to 300,000 event logs can be
stored in the RTU if LP1/2/3 Exp.
Memory is ticked. Event logs stored in
expanded memory can only be
uploaded using Toolbox 32.
Port List – Select button 2 (for port
2). Set Module to CP-x P2.
If a PSTN modem, Radio, GSM,
RS485 communications or an option
board is being used, please see the
Port Configuration chapter for more
essential settings.
7.
Download the configuration file into
the LP-2/3 using Configuration,
Download RTU Configuration.
8.
When firmware drivers are required
(eg. for paging, Modbus, DNP3), they are
always downloaded into SRAM (battery
backed memory).
After an RTU configuration is downloaded
into the LP-2/3 that allocates memory for
firmware drivers, the drivers can then be
downloaded.
LP-1/2/3 drivers use the file extension
DHI and are available from www.cse-
semaphore.com/mykingfisher