#YPDSTAT
(LP-2/3)
#YPDSTAT is defined differently for LP-x RTUs than for other types of
Kingfisher RTUs as follows:
Configuration:
#YPDSTAT Wakeup Conditions (integer read/write)
Ch 1 Time wakeup (default setting. Always set when #YPDTIME is
set)
Ch 2 Digital input 1 change of state
Ch 3 Digital input 2 change of state
Ch 4 Not Used
Ch 5 Port 1 CTS change (default setting)
Chs 6-15 Not Used
Ch 16 Sub-active sleep mode.
The LP-2/3 remains in sleep mode while counting pulses from digital
inputs 1 or 2. e.g. Can enter sub-active sleep mode by writing 16#8010
(8010 Hex) to #YPDSTAT (this will allow the LP-2/3 to count pulses and
will also enable wakeup on port 1 CTS change). 5V Out, V1 Out and 24V
Out are also disabled in this mode
#YRELAYRTU
The RTU address of the last Series I RTU that a message was relayed
to. This parameter can be used by a master RTU that relays output
messages from a computer.
Read
#YRTUTYPE
RTU processor type. 1 = CP-1, 2 = PC-1, 3 = CP-10/11, 4 = CP-21, 5 =
SBX, 6 = ERS Micro, 7 = LP-1/2/3, 8 = SB-1, 9 = Micro-4
Read
#YSOCKET
x
(CP-21 only) Returns the network usage of the 24 possible CP-21
Ethernet sockets (where x=socket number) on the LAN. 0=not used, 1-
255=the address of the RTU using that socket.
Read