#YFLAGS.
cc
General RTU operation flags
Ch1 1 = Scan overrun. Scan overrun is a status indication only and
does not affect RTU operation. Triggered when the RTU cannot
read all the IO modules and process the ladder logic at the
configured rate (Configuration, System Parameters - IO Scan
Interval).
Read
Ch2 1 = Driver error. There was a CRC error in the firmware driver.
This bit is set or reset after a warm start.
Read
Ch3 1 = Currently synchronizing the clock. Read
Ch4 1 = The maximum number of TX_IMAGES are active at this
moment. Updating network register blocks in the destination RTU
requires a considerable amount of network management. When
the network management registers are fully used, this bit is set.
This would only occur when trying to run multiple TX_IMAGES
blocks simultaneously.
Read
Ch5 1 = Ladder error. CRC failed. Read
Ch6
1 = Log overrun. Log Overrun is a status indication only and does
not affect RTU operation. Triggered when the memory allocated
for event logs is full and the oldest event logs are being
overwritten.
Read
Ch7 1 = Message buffer full. The message buffer is full and no new
messages can be initiated or received. The message buffer can
contain a maximum of 32 messages. Occurs when messages are
continuously generated faster that they can be transmitted OR
after sending two or more pager messages for CPU firmware
prior to 1.43d. Flag is cleared when RTU is warm started.
Read
Ch8 1 = Pack event logs function active Read
Ch9 1 = Network data overflow (same as #YDIAG.16) Read
Ch10 1 = Tx DNP3 active Read
#YIMPL.
cc
Firmware Implementation. Firmware is available with a number of
communication options.
Ch1 1 = Form 4C Recloser Read
Ch2 1 = ADS Data Logger Read
Ch3 1 = TMR Radio Read
Ch4 Not Used Read
Ch5 1 = Redundancy Read
Ch6 1 = MAC-800 RTU Read
Ch7 1 = Microtran Read
Ch8 1 = Minitran Read
Ch9 1 = Inline Flow Computer Read
Ch10 1 = Email Modem Switch Unit Read
Ch11 1 = Paging Read
Ch12 1 = Gas and Fuel Minitran RTU (Minitran 1) Read
Ch13 1 = Omron PLC Read
Ch14 1 = Gas Calculation AGA8 Read
Ch15 1 = Hohner Shaft Encoder Read
Ch16 1 = Steam flow calculation AGA9 Read
#YLOGIDX
Event log current index pointer (0-65535). Each new event log is stored
at the location pointed to by this register and then the register is
incremented to the next event log location. Note: the event log list is a
circular buffer. When the buffer is full, the oldest event logs will be
overwritten.
Read/Write
#YMATHSTAT
Maths error status register. 0 = Maths OK. Read