#DO6.2 Analog input 2 live zero 0 0=0-5 V, 1=1-5 V Read/Write
#DO6.3 Analog input 3 live zero 0 0=0-5 V, 1=1-5 V Read/Write
#DO6.4 Analog input 4 live zero 0 0=0-5 V, 1=1-5 V Read/Write
#AO3.9,
#AO3.10
Pulse 1 (DI1) or pulse 2 (DI2)
debounce time respectively
0 0 to 32000 ms debounce time
The pulse must remain in the
active state for the debounce time
before a pulse is counted
(0 = no debounce).
Read/Write
#AO4.2,
#AO4.3,
#AO4.4,
#AO4.5
Analog input 1 to 4 average
sample count respectively
1 1-59 samples. Number of
samples to average the analog
input over before updating the
analog input data register. Each
sample takes up to 110 ms.
Read/Write