User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
258
LP-1/2/3
Note: Only read/write hardware registers listed here should be written to. Other hardware registers are used
by the LP-1/2/3 firmware and care must be taken not to overwrite these.
LP-1/2/3 I/O Registers
Register Description Comments Read/Write
#DI1.1 Digital input 1 0V or Open =OFF. Pulse input 1 Read
#DI1.2 Digital input 2 0V or Open =OFF. Pulse input 2 Read
#DI1.3 Digital input 3 0V or Open =OFF. Read
#DI1.4 Digital input 4 0V or Open =OFF. Read
#DI1.5 Digital input 5 0V or Open =OFF. Can be used as output #DO2.3 Read
#DI1.6 Digital input 6 0V or Open =OFF. Can be used as output #DO2.4 Read
#DI1.7 Digital input 7 0V or Open =OFF. Can be used as output #DO2.5 Read
#DI1.8 Digital input 8 0V or Open =OFF. Can be used as output #DO2.6 Read
#DO2.1 Digital output 1 Latched relay output (1 = closed) Read/Write
#DO2.2 Digital output 2 Latched relay output (1 = closed) Read/Write
#DO2.3 Digital output 3 Optional Transistor output (1 = closed ie. sink to 0V) Read/Write
#DO2.4 Digital output 4 Optional Transistor output (1 = closed ie. sink to 0V) Read/Write
#DO2.5 Digital output 5 Optional Transistor output (1 = closed ie. sink to 0V) Read/Write
#DO2.6 Digital output 6 Optional Transistor output (1 = closed ie. sink to 0V) Read/Write
#AI1.2 Analog input 1 12bit, 0-32760 = 0-100% Read
#AI1.3 Analog input 2 12bit, 0-32760 = 0-100% Read
#AI1.4 Analog input 3 12bit, 0-32760 = 0-100% Read
#AI1.5 Analog input 4 12bit, 0-32760 = 0-100% Read
#AI2.4 Pulse counter 1 0-65535 pulses. Write 0 to #AO2.4 to reset Read
#AI2.5 Pulse counter 2 0-65535 pulses. Write 0 to #AO2.5 to reset Read
AO5.4 Analog Output 1 15 bit, 0-32767 = 0-100%. LP-3 Only. Read/Write