User manual

Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
257
Analog Inputs
(ss = slot address 1-64)
Module
Register
(ss = slot 1-64)
Raw
Scale
Eng. Units
Read
Write
Description
PSU1 V0
#AIss.2: 0-32640 0 to 32.27V Read Supply voltage to power supply
#AIss.3: 0-32640 -2 to +2 A Read Battery charging current
#AIss.4: 0-32640 0 to 32.27 V Read Battery Voltage
#AIss.5: 16128-
32640
-25 to +227°
C
Read Module temperature
PSU1 V1
#AIss.2: 0-32640 0 to 32.27V Read Supply voltage to power supply
#AIss.3: 0-32640 -2 to +2 A Read Battery charging current
#AIss.4: 0-32640 0 to 32.27 V Read Battery Voltage
#AIss.5: Signed;
-18688 to
32576
(0°C=0)
-55 to +125°
C
Read Module temperature
PS
-
1
#AIss.2: 0-32736 0 to 32.27V Read Supply voltage - the DC voltage supplied to
the RTU modules on the backplane
(typically 12V) and used to charge the
battery. This voltage is sourced from the
battery if there is no input supply present.
#AIss.3: 0-32736 -4 to +4 A Read Battery charge/discharge current. Current
is positive when charging.
#AIss.4: 0-32736 -4 to +4 A Read Total current supplied by the power supply
to the RTU modules and battery.
#AIss.5: 0-32736
(0°
C=6528)
-20 to +80°C
Read Module temperature