PS-10/11/20/21
Register
(ss = slot 1-64)
Raw
Scale
Eng. Units Read
Write
Description
#AIss.2 0-32736
0 to 32.27V Read Supply voltage - the DC voltage supplied to the RTU
modules on the backplane (typically 12V) and used to
charge the battery. This voltage is sourced from the
battery if there is no input supply present.
#AIss.3 0-32736
-4 to +4 A Read Battery charge/discharge current. Current is positive
when charging.
#AIss.4 0-32736
-4 to +4 A Read Total current supplied by the power supply to the RTU
modules and battery.
#AIss.5 0-32736
-20 to +80 °C
0 °C = 6547
Read Battery temperature (uses external temperature sensor
if present, otherwise returns the same value as
#AIss.14)
#AIss.7 N/A N/A Read [PS-11/21 only] Configured Battery parameters
Chs 1-8 = Battery Type.
0 = Default, 1 = Lead-Acid, 2 = Ni-Cad
Chs 9-16 = Battery Size (x 0.1AH)
0 to 250 = 0 to 25.0AH Max.
#AIss.14 0-32736
-20 to +80 °C
0 °C = 6547
Read Module temperature (PS-11/21 only).
#DIss.1 N/A N/A Read ON = AC Power ON (PS-10/11 only)
ON = DC Input Power ON (PS-20/21 only)
#DIss.2 N/A N/A Read ON = Aux 24V Failure or Not Present
#DIss.3 * N/A N/A Read ON = Battery NOT Low, OFF = Battery Low
#DIss.4 N/A N/A Read [PS-11/21 only] Power supply model
ON = PS-21, OFF = PS-11
#DIss.5 N/A N/A Read ON = Float State
#DIss.6 N/A N/A Read ON = Charge State
#DIss.7 N/A N/A Read ON = Boost State
#DIss.8 N/A N/A Read ON = Temperature Sensor Error
#DOss.9 N/A N/A Read
Write
ON = Manual control of radio and 24V power
(and Mains Supply for PS-11)
OFF = Automatic control (default)
#DOss.10 N/A N/A Read
Write
ON = Set Radio power OFF (only when manual control
enabled)
#DOss.11 N/A N/A Read
Write
ON = Set Aux 24V OFF (only when manual control
enabled)
#DOss.12 N/A N/A Read
Write
ON = Inhibit PS-11 AC Supply Input Circuit (only when
manual control enabled)