Exception Reporting from a G3 to a Kingfisher PLUS+ RTU
When a G3 exception reports it sends the first 12 registers as detailed below.
G3 Kingfisher Registers
Register * Description
#NRrrr.1 Ch 1 (LSB) = Digital input 1 status
Ch 2 = Digital input 2 status
#NRrrr.2 Analog input 1. 0-26208 = 0-100% = 0-20mA or 4-20mA
For over-range:
0-20mA input: 0-32760 = 0-125% = 0-25mA
4-20mA input: 0-34398 = 0-131.25% = 4-25mA
#NRrrr.3 Analog input 2. Same range as above.
#NRrrr.4 General alarms
Ch 1 ON = Comms Fail
Ch 2 ON = Low Voltage alarm
Ch 3 ON = Incorrect PIN alarm
#NRrrr.5 Supply Voltage to the G3 (0 to 300 = 0.0 to 30.0V)
#NRrrr.6 SS radio received signal strength. There are two ranges depending on which type of
radio is installed.
0= no signal received
9XTend radio (900MHz): -110 (weak) to -40 (strong) dBm
24XStream radio (2.4GHz): 6 (weak) to 54 (strong)
The 9XTend signal strength is stored as
65426 to 65496 (unsigned) = -110 to -40 (signed) dBm.
#NRrrr.7 G3 internal temperature. -20 to 70°C (already scaled)
#NRrrr.8 Status indications
Ch 1 ON = IO Scanning ON
Ch 2 ON = if G3 in override mode, IO data has changed.
Ch 3 ON = log buffer is >90% full (=900 logs)
Ch 4 ON = new counter 1 value
Ch 5 ON = new counter 2 value
(Remote G3 sends counter value and then resets it back to zero)
#NRrrr.9 and
#NRrrr.10
Counter 1. 32-bit long integer (1 to 4,294,967,296)
#NRrrr.11 and
#NRrrr.12
Counter 2. 32-bit long integer (1 to 4,294,967,296)
#NRrrr.13 Counter periods. Used by remote G3 for frequency generator outputs.
Ch 1 - 15: Index into counter table
Ch 16 ON = Use table (ms): 500, 1000, 5000, 30 000, 60 000, 90 000, 180 000, 360
000, 86 400 000
Ch 16 OFF = Use table (s): 0, 60, 3600, 21 600, 43 200, 604 800
#NRrrr.14 Ch 1 = DO1 raw output state – Read/Write
#
Ch 2 = DO2 raw output state – Read/Write
#
#NRrrr.15 AO1 raw output value. 0-26208=0-100% - Read/Write
#
#NRrrr.16 AO2 raw output value. 0-26208=0-100% - Read/Write
#
#NRrrr.17 Ch 1 = DO1 actual output state - Read only
Ch 2 = DO2 actual output state - Read only
#NRrrr.18 AO1 actual output value. 0-26208=0-100% - Read only
#NRrrr.19 AO2 actual output value. 0-26208=0-100% - Read only
*
rrr = G3 address
#
The raw outputs are modified by the G3 output options before the actual output is set.