User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
236
Ethernet Configuration
The following parameters can be used to control the operation of the RTU’s Ethernet ports:
#YPST
nn
.7
(nn=port number 1 to 16)
1 = Link Active (CP-1x or MC-1x ports only). Note: supported by
Ethernet T option boards version 1.1 and newer (port is labeled
E'NET-T 1.1)
Read only
#YPST
nn
.12
(nn=port number 1 to 16)
0 = Use fixed UDP destination port based on port protocol [default]
1 = Use dynamic UDP destination port. Required when using Citect
6.x+.
Note: this parameter is not supported by MC-10/11 Ethernet ports
Read/Write
Post Tx
(configured for a port from
Configuration, Port List)
The inactivity timeout for each Ethernet socket. Once the socket has
been inactive for this time setting, the socket will be closed.
Implemented in CP-10/11/12 firmware 1.43d, CP-21 firmware 1.45e
and MC-11/12 firmware C153 or newer. Also LP-2/3 firmware 1.50e
Read/Write
CP
-
21 Ethernet
CP
-
10/11
/12
, MC
-
10/11
/12
LP
-
2/3
Ethernet
Post Tx Socket Timeout (s) Post Tx Socket Timeout (s)
0 60,000 [default] 0 60 [default]
1 to 9 10 1 to 600 1 to 600
10 to 600
10 to 600 > 600 600
> 600 600
#YLST
rrr
.11
(rrr=remote RTU address)
1 = Close socket connection (CP-1/121 or MC-11/12 ports only).
W
hen set, forces the RTU to close the existing socket connection for
a remote RTU. When a new message is initiated, the new network
link settings will then be used (useful for creating a redundant
comms path).
Read/Write
#YMODE.4
1= Keep Ethernet port open on the redundant standby CPU. The
duty and standby CPUs can both have their Ethernet port working
simultaneously as long as they are configured with different Ethernet
addresses (allows support for redundant LANs).
Read/Write
#YSOCKET
x
(x=socket number 1 to 24)
(CP-21 only) Returns the network usage of the 24 possible CP-21
Ethernet sockets on the LAN. 0=not used, 1-255=the address of the
RTU using that socket.
Read only
#YLIPADLrrr
(rrr=remote RTU address)
(0-65535) Lower half of IP address A.B.C.D. Chs 1-8=C, Chs 9-
16=D. To set C and D, use #YLIPADLrrr=C+256xD.
Read/Write
#YLIPADHrrr
(rrr=remote RTU address)
(0-65535) Higher half of IP address A.B.C.D. Chs 1-8=A, Chs 9-
16=B. To set A and B, use #YPIPADHrrr=A+256xB.
Read/Write