Symptom Probable Cause Remedy
RTU loses
configuration
and ladder logic
when powered
Internal battery is flat Return to Semaphore for replacement of internal battery.
RTU loses
configuration
and ladder when
powered down
Battery link not installed Fit a link on the back of the processor module. For the PC-1,
fit the link across the upper 2 pins.
Modules in
wrong slots in
hardware
overview
Incorrect backplane dip
switch settings
Adjust backplane dip switch settings to the correct backplane
rack. Turn power off and on again.
Timing is
incorrect
RTU Real Time Clock is not
set
Set the RTU Real time clock to the current time using
Toolbox.
Battery link is not fitted Fit a jumper on the back of the processor module. For the
PC-1, fit the jumper across the upper 2 pins.
RTU cannot
send pager
messages using
a modem
Modem is not correctly
configured
Disable any error correction and compression settings in the
modem (ie. use \N0 in the initialisation string).
RTU Will Not
Dial / Cannot
connect to a
remote RTU
using a PSTN
modem
RTU is not configured
correctly / Modem is faulty
or incorrectly configured
Use Comms Terminal to check that the local modem is
connected and powered up correctly. Please see Utilities,
Comms Terminal for more information.
Check local RTU port is correctly configured. Eg.
Type=PSTN, Baud Rate=9600, Pre Tx=0, Post Tx=0
(PSTN modem or GSM) or Post Tx=400 ms (for 3G
modem). Ensure correct Init String is being used for the
PSTN port (select the Configure button).
Check the Network list is correct. Ensure
Timeout=2000ms (or greater) and that the correct port
number (as configured above) is being used to dial the
remote RTU.
Check the Phone Directory. Ensure phone numbers are
added for the Target (remote) RTU address.
Create a test site - create a Network List entry for Target
RTU 100. Then add a phone number of a local phone
(eg. a mobile phone) for Target RTU 100 in the Phone
Directory.
Test if the local phone will ring, use Utilities, Dial Site to
dial site 100.
Manually dial the phone number of the remote RTU using
a local phone to check that the remote modem will
answer.
Check if the local RTU will connect to the remote RTU by
using Utilities, Dial Site to dial the remote RTU. Ensure
the configuration for the remote RTU is loaded in
Toolbox. Once connected, select the configuration
window of the remote RTU and then select View, RTU
Status.