The IO-4 is to be calibrated for a strain gauge input used to measure the water level in a tank. The tank has
a depth of 5m. Note: it is more accurate if the strain gauge is calibrated when the tank is full.
Select the Reset Calibration button.
Select the Enable Calibrate button.
For the first input, lift the strain gauge out of the water (this will probably produce a voltage of about 1mV
into the IO-4).
Enter 0% (corresponding to an empty tank) in the box above the Accept Perc 1 button and then select
Accept Perc 1.
Put the strain gauge back into the water to a known depth of say 2m (this may produce a voltage of say
11mV into the IO-4. The actual voltage will depend on the calibration of the strain gauge). If the tank is
full then put the strain gauge all the way into the tank.
Enter 40% (corresponding to 40% of 5m = 2m or enter 100% if the tank is full) in the box above the
Accept Perc 2 button and then select Accept Perc 2.
Select the Send Calibration button. The IO-4 module is now calibrated.
IO-4 Module V1.2
The original IO-4 module (version 1.2) allows channel 1 to be calibrated using fixed percentage setpoints of
0% and 100%. The hardware overview for an IO-4 module, version 1.2 is shown below
Figure: Hardware Overview For The IO-4 Module V1.2
Calibration Method:
Select the Reset Ch.01 button. This will clear the calibration registers in the IO-4 module.
Select the Enable Ch.01 button. This tells the RTU that channel 1 is about to be calibrated.
Apply the first voltage input corresponding to 0% to channel 1 (0-50mV).
Select Set Ch.01 Min.
Apply the second voltage input corresponding to 100% to channel 1 (0-50mV).
Select Set Ch.01 Max. The IO-4 is now calibrated.