For example, an RTU can be configured to switch its output voltages on after 5 minutes, wait two seconds,
scan all the IO modules for 10 seconds and then switch off its output voltages. The time intervals used in this
process are configured using the following parameters:
• Interval: The period of time (in seconds) that the output voltages are switched off for. To disable Power
Saving Control, set Interval to zero.
• Warmup Time: The period of time after the output voltages are switched on that is waited before
scanning the IO modules.
• Sample Time: The period of time that the IO modules are scanned for after the Warmup Time has
expired. The Power Saving Control cycle is then repeated Interval seconds after the Sample Time has
expired.
During the Interval and Warmup Time periods, the IO is not scanned. The IO values obtained from the last
Sample Time period are maintained.