User manual

Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
193
Recovering A CP-10/11 After Downloading MC Firmware
An MC-10/11 uses the same circuit board as a CP-10/11 and so it is possible to download MC firmware into
a CP module. This will change a CP-10/11 into an MC-10/11 (even though the module lens still says CP-
10/11!) To recover a CP-10/11 after downloading MC firmware, please follow the steps below.
1.
Connect to Port 1 of the CP-
10/11 module (that contains the
MC firmware)
CP11
Port 1
2.
Select Utilities, Advanced,
Download CPU Firmware
3.
Set RTU address to 0 and
then select OK
4.
When the message
“ERROR: Cannot Communicate
with RTU” appears select Ignore
5.
Select the CP-10/11
firmware file to download and
then select OK
Note: ensure List files of type is
set to CP-10 firmware files (as
shown highlighted)