Utilities - Advanced
Options: Download CPU Firmware, Download MC Firmware, Download Firmware Driver, Upload
Configuration, Cold Start, Swap Master, PC System ID, Read/Write System Register and Upload Memory.
Utilities - Download CPU Firmware
Firmware in CPU modules can be upgraded to add new features and enhancements.
The firmware version that is running in the CPU module is displayed in the RTU Status window.
Caution! An RTU is cold started after downloading CPU firmware. Firmware can be downloaded to a
remote RTU but it is possible that communications will be lost after the RTU is cold started. Note: the RTU
will remember the configuration settings for its ports as follows;
• PC-1 - Ports 1-8
• CP-11/21 - Ports 1-4
• CP-12 - Ports 1-4
Do not hot swap any module on a connected rack while downloading firmware.
MC Firmware must be downloaded via the first port of any MC module.
Downloading processor firmware or drivers requires a reliable connection to a port that is retained after a
cold start.
Configuration, logic and ladder can be downloaded via any port, including via remote RTUs, providing a
reliable connection exists.
1.
To download firmware to the
local CPU, connect to Port 1 of
the CPU.
To download firmware to a
remote CPU, connect to any
serial port on the local RTU (a
communications link is required
between the local RTU and the
remote CPU).
CP11
PC1
Port 1 Port 1
Port 1
Redundant Processors: please ensure only one processor is
installed on the backplane while upgrading firmware
2.
Select Utilities, Advanced,
Download CPU Firmware
3.
To download firmware to the
local CPU set RTU address to 0
and then select OK
To download firmware to a
remote CPU set RTU address to
the address of the remote CPU
and then select OK
Toolbox will check if it can
communicate with the RTU
address specified.