View - RTU Status
Displays the operational state of the RTU.
RTU Address: (1 to 249) Address of the RTU that Toolbox is communicating with.
Processor Type: PC-1, CP-1, CP-10/11, CP-21, SBX, ERS Micro, LP-1/2/3, SB-1 or Micro-4.
RAM Size: Battery backed RAM size.
Firmware Version: Version of the operating code as stored in flash memory.
I/O Processing: Enabled or Disabled. Status of IO module scanning.
Ladder Processing: Enabled or Disabled. Status of ladder logic processing.
Netblocks Used: The number of network register blocks that have been used. The total number of network
blocks that are available can be checked by selecting the Check memory usage button in Configuration,
Memory. If the maximum limit is exceeded a Netblks Overrun system flag is displayed.
Date, Time: Real time clock settings in the RTU. The displayed time is updated every time Toolbox polls the
RTU. The polling rate is determined by the Comms Repeat Rate setting in Configuration, PC Setup.
I/O Scan Rate (scans/sec): Rate of scanning the IO modules and processing ladder logic (if enabled).
System Flags: General RTU operation flags (from the system register #YFLAGS ). Note: the flags Scan
Overrun and Log Overrun are status indications only.
Firmware drivers included: The names of firmware drivers and special functions that have been
successfully loaded in the RTU. Some drivers are included in firmware (eg. Redundancy). CP-21 has most
drivers included in firmware.