User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
169
Communicating With A Trio E-Series Radio
When using an Rx Trio_E block, the RTU should be configured as follows:
• First ensure that the Trio E-Series Radio driver is supported by the type of RTU that is being used and
that the latest firmware and driver are loaded in the RTU (as detailed in protocols.pdf available from
www.cse-semaphore.com/mykingfisher).
• From Configuration, Port List configure the port for the correct baudrate (Trio radio default is 19200)
and set the port protocol to TRIO Eseries.
• Assign an address to the Trio radio and add this address to the network list in Configuration, Network
List (this must be a unique address in the RTU network).
• Configure an RX TRIO ladder block to poll the local or remote Trio radio. To poll the local radio set Radio
ID to 0. To poll a remote Trio radio set Radio ID to the serial number of the remote radio.
• Both ports of the local Trio radio must be used if the radio is also used for RTU to RTU communications.
Trio radio port A is used for RTU to RTU communications while Port B allows the radio data to be polled.
TRIO
RADIO
450-ER
CP11
PS11
Port A: RTU to RTU
communications
Port B: Trio Data port