User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
168
Driver - Trio E-Series Radio
Rx Trio E-Series Radio
Reads status or statistical information from a Trio E-Series radio.
Comment: A 12-character description.
RTU # (1-255): Address assigned to the Trio radio. Data returned from the Trio radio is stored in network
registers corresponding to this address.
Radio ID: (0 or long constant) When set to 0, communicates with the local radio. Otherwise set to the serial
number of the target radio. Specifying 0 will allow the local radio to be replaced without having to update the
RTU configuration each time.
Command: (Read Status Data or Read Statistics Data) Returns data as follows (where #Rx is the
Destination Register defined below):
Read Status Data (returns eight 16-bit signed registers)
Data Description
Register
Units
Exa
mple
Temperature #Rx 0.1 Deg C 245 = 24.5 deg C
Signal Indicator (RSSI) #Rx+1 0.1 dBm -701 = -70.1dBm
Fwd Tx Power (Remote) * #Rx+2 0.1 dBm 204 = 20.4 dBm
Supply Volts #Rx+3 0.1 V 138 = 13.8 V
Rx Freq Error #Rx+4 0.1 Hz 254 = 25.4 Hz
Rev Tx Power (Remote) * #Rx+5 0.1 dBm 77 = 7.7 dBm
Fwd Tx Power (Base Station) * #Rx+6 0.1 dBm 126 = 12.6 dBm
Rev Tx Power (Base Station) * #Rx+7 0.1 dBm 34 = 3.4 dBm
* If connected to a base station radio, the Fwd and Rev Tx Power (Remote) fields will be set to 0. Similarly, if connected
to a remote radio, the Fwd & Rev Tx Power (Base Station) fields will be set to 0.
Read Statistics Data (returns four 32-bit long registers)
Data Description
Register
Bad Frame Count #Lx
Good Frame Count #Lx+2
Lost Sync Count #Lx+4
Lost RSSI Count #Lx+6
Destination Register: (#R1 to #R2048) Specified as a local register but indicates the first network register to
begin storing the data from. When the Read Statistics Data command is being used, an odd numbered local
register should be specified (#R1, #R3…#R2047) to allow the received data (in Long format) to be correctly
displayed using Toolbox.