Command Received Data
Read uncorrected
volume
#R23 least significant word of uncorrected volume
#R24 most significant word of uncorrected volume
#R25 uncorrected volume flags
#R25.8 1=cubic feet, 0=m3
Read corrected
volume flow rate
#R27 least significant word of flow rate.
#R28 most significant word of flow rate.
#R29 daily usage flags
#R29.8 1=cubic feet, 0=m3
Read volumes at end
of the day
#R31 day of month of volumes
#R32 month of the volumes
#R33 least significant word of corrected volume
#R34 most significant word of corrected volume
#R35 least significant word of uncorrected volume
#R36 most significant word of uncorrected volume
#R37 volume flags
#R37.8 1=cubic feet, 0=m3
Read maximum
hourly demand
#R40 hour of maximum hourly demand
#R41 day of week of maximum hourly demand
#R42 day of month of maximum hourly demand
#R43 least significant word of maximum hourly demand
#R44 most significant word of maximum hourly demand
Read maximum daily
demand
#R45 day of week of maximum daily demand
#R46 day of month of maximum daily demand
#R47 least significant word of maximum daily demand
#R48 most significant word of maximum daily demand
Read current hourly
usage
#R51 least significant word of hourly usage
#R52 most significant word of hourly usage.
#R53 hourly usage flags
#R53.8 1=cubic feet, 0=m3
Read current daily
usage
#R55 least significant word of daily usage
#R56 most significant word of daily usage.
#R57 daily usage flags
#R56.8 1=cubic feet, 0=m3
Communicating With An Inline flow computer
When using an RX_INLINE block the RTU should be configured as follows:
First ensure that the Inline driver is supported by the type of RTU that is being used and that the latest
firmware and driver are loaded in the RTU (as detailed in protocols.pdf available from www.cse-
semaphore.com/mykingfisher).
Set the port protocol as INLINE or INLINE2 in Configuration, Port List. INLINE2 is the newer Inline
protocol. Note: the Inline driver must be configured on a serial port.
Set the port baudrate in Configuration, Port List.
Add the Inline flow computer address to the network list in Configuration, Network List (this should be
a unique address in the RTU network). Also set the message time out to at least 3000 ms.
Ensure that the RTU has the correct time and date to allow the RTU to read the volumes at the end of
the day.