User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
149
Driver - Inline Flow Computer
Rx Inline
Receives one data parameter from an Inline flow computer.
Comment: A 12-character description.
RTU #: (1-255) The RTU address assigned to the Inline flow computer (note: addresses 250-255 are
reserved for paging and PC use).
Command: The data parameter to read. The available options are: read RTC (real-time clock), read
pressure, read temperature, read corrected volume, read uncorrected volume, read correction factor, read
maximum hourly demand, read maximum daily demand, read current hourly usage, read current daily usage,
read volumes at end of the day and read flow rate.
The data returned from the Inline flow computer is placed in the network registers of the corresponding RTU
address. The network registers that are used for each command are shown below.
Command Received Data
Read real-time clock #R1 seconds, 0-59
#R2 minutes, 0-59
#R3 hours, 0-23
#R4 day of week, 1-7 (1 = Sunday)
#R5 day of month, 1-31
#R6 month, 1-12
#R7 year, 0-99
Read correction
factor
#R9 least significant word of correction factor
#R10 most significant word of correction factor
Read pressure #R11 least significant word of pressure
#R12 most significant word of pressure
#R13 pressure flags
#R13.8 1=Manual, 0=Auto
#R13.7 1=Error
#R13.6 1=Gauge, 0=Absolute
#R13.5 1=PSI, 0=kPa
#R13.4 decimal point: 1 = x 0.01 , 0 = x 0.1
Read temperature #R15 most significant word of temperature
#R16 least significant word of temperature
#R17 temperature flags
#R17.8 1=Manual, 0=Auto
#R17.7 1=Error
#R17.6 1=Deg F, 0=Deg C
Read corrected
volume
#R19 least significant word of corrected volume
#R20 most significant word of corrected volume
#R21 corrected volume flags
#R21.8 1=cubic feet, 0=m3