Instruction manual
Model DCP-NextG Digital Cell Phone Kit
10
To connect a new CS I/O modem kit to a data logger, follow these steps:
Connect the black DCP-SAM3GPLUS-CBL’s square RJ45 connector to the socket
on the modem.
Connect the two tinned wires on this cable to the data logger. The red wire connects
to 12V and the black wire to the G terminal. The SW12 terminal can be used instead
of 12V however since it is a switched supply it needs to be enabled in the
datalogger program to function correctly.
Note that SW12 is a switched 12V supply and needs to be enabled in the data logger
program to function.
Insert the 9-pin end of the DCP-SAM3GPLUS-CBL into the RS-232 (DCE)
connector on the SC932A.
Finally, connect the male end of the SC12 cable to the logger’s CS I/O port and one
of the female ends (doesn’t matter which) to the CS I/O connector the SC932A
Ensure that the SC932A interface is connected correctly!
It is easy to connect the SC932A the wrong way around – it will not work unless the DCE
Device end is connected to the modem and the Datalogger end is connected to the logger’s
CS I/O port.
The CSIO-SAM3GPLUS-CBL cable must be used between the SC932A device and the
modem for successful communication between the data logger and the modem. The
manufacturer’s beige interface cable with the female RS-232 connector is not suitable for this
connection.