main flame only, then it may be necessary to advance the pointer on the burner
control arm from “LO” to the first casting mark, towards the “HI” fire position.
Under normal operating conditions this will open the gas butterfly valve sufficiently
to produce a minimum main flame, independent of the pilot flame. This is accom-
plished by adjustment of the linkage between the control operator and the burner
crank. It will be necessary to move the toggle on the control motor arm in towards
the motor shaft to reduce the radius slightly so as to prevent the burner control arm
from moving past the casting “HI” mark.
Operating instructions
The operating instructions below are provided only as a guide-line and
are not intended to replace those provided by the manufacturer of a
complete system of which the INDITHERM burner is only a part. Where
applicable, instructions provided by the system's manufacturer shall
take precedence.
To start
(automatically)
Open main gas and pilot gas cocks.
Push start or pilot button.
To start
(manually)
Make sure that safety shut-off valve, main gas and pilot gas cocks are closed.
Make sure the burner firing rate control handle is at predetermined low fire position.
Start air circulating and exhaust fans.
Energize system control panel, if applicable.
Start burner blower motor.
Open main gas and pilot gas cocks.
Press start button (pilot solenoid valve should open to allow pilot ignition).
Main gas valve will open (only when all safety circuits are complete).
To stop
(automatically or manually)
Close main gas and pilot gas cocks.
Burner continues operating until flame extinguishes (can be observed through
observation port at the rear of the burner). Safety shut-off valve and solenoid valve
should automatically close.
De-energize system control panel as well as the burner blower motor.