Series 92 Electronic Gas Modulation System
See Bulletin MMR_MT_EN for additional M/MR valve information
NOTE: Low Fire Adjustment should be checked whenever High
Fire Adjustment is changed.
High Fire Adjustments
Rotate selector dial to maximum temperature setting.
NOTE: Voltage to the valve must be at least 18VDC.
Adjust separate pressure regulator to obtain desired manifold
pressure.
Low Fire Adjustments
Disconnect a wire from M valve terminal block.
NOTE: Be careful not to allow wire to come in contact with any
other part.
Remove by-pass cap (A) and turn screw (B) using small
screwdriver to desired low re adjustment. (See Figure 1)
NOTE: Clockwise Screw rotation reduces ow rate. Do not
overtighten.
VALVE ADJUSTMENT
Ambient Limits
Operating: 32° to 131°F (0° to 55°C)
Non Operating: -4° to 158°F (-20° to 70°C)
Modications
Models M420, M520, M620 are available as “W” models -
indicates covered wire terminal connections.
Models M420, M520, M620 are available with side pressure
tap for reading outlet pressure - on side opposite of minimum
adjustment mechanism.
Valve Mounting
Valve must be mounted in upright position in horizontal pipe run,
downstream of all other controls except high pressure cut-off
switch if used.
Optional T115 Room Override Thermostat
As an optional component, an independent room override
adjustment can be provided to permit setting of the override
temperature from 0° to 40°F above the TD92 setpoint. The
T115 override thermostat senses room temperature and resets
the discharge air to a higher temperature whenever the sensed
temperature falls below the T115 setting.
The standard conguration is to connect the T115 override
thermostat to the TD92 remote temperature dial. In some cases
it may be more convenient to connect the T115 to the A1092
amplier. The T115 may be connected directly by removing the
jumper on the amplier’s input terminal block and connecting
the T115 in its place. The jumper must then be installed across
the TD92’s override terminals for proper operation. See Wiring
Diagrams (Figures 2 - 8).
SPECIFICATIONS (cont.)
Figure 1: Valve Adjustment
© 2012 Maxitrol
© 2012 Maxitrol
B
A
WIRING DIAGRAMS
Figure 2: Standard Connection of A1092 without Override Thermostat
JUMPER NOT REQUIRED ACROSS
TERMINALS 11 & 12