Product Overview

Additional relays and timers external to SC30 can be replaced
with TR1 - Timer Relay Control. See TR1_MI_EN.
Modulator and modulator-regulator valves are available up
to 5 psi (350 mbar) inlet pressure, 30,000 CFH (850 m3/h)
maximum, and pipe sizes from 3/8” to 4”. (For additional valve
information see Bulletin MMR_MT_EN, or consult your Maxitrol
sales representative.)
SC30 Series Signal Conditioners
READ PRIOR TO INSTALLATION: To Avoid Internal Damage to
SC30 Series Signal Conditioners Follow These Guidelines.
1. Transformer secondary must not be grounded in any portion
of the circuit external to the SC30 Series signal conditioners.
A separate, independent transformer is recommended.
2. Multiple SC30 Series signal conditioners controlled by a signal
source with common outputs (terminals 7 & 8) require separate
transformers for each SC30 Series signal conditioner.
3. Multiple SC30 Series signal conditioners powered by a single
transformer require independent signal inputs (terminals 7 &
8) to each SC30 Series signal conditioner.
For Indirect Fire Gas Applications Using 2-speed Inducers and 2-stage Gas Valves
Maxitrol Company
23555 Telegraph Rd., P.O. Box 2230
Southeld, MI 48037-2230 U.S.A.
www.maxitrol.com
© 2012 Maxitrol Company,
All Rights Reserved.
SC30_MS_EN_09.2012
Figure 1: SC30 Series Signal Conditioner
SPECIFICATIONS
DIMENSIONS: 4.75“ W x 3.38“ H x 2.09“ D
SIGNAL CONDITIONER
Ambient Limits ................. -40º to 150ºF (-40º to 66ºC)
SIGNAL CONDITIONER POWER REQUIREMENTS
24 VAC transformer, 20 VA capacity (50/60 Hz).
(No grounded secondary.)
Figure 2: Wiring Diagram
DESCRIPTION
The track mounted SC30 Series controls three functions:
1) Converts a controllers DC output signal of 0-10 volts to a
0-20 VDC signal to provide compatibility with Maxitrol’s M/MR
Series gas valves.
2) Controls the normally open relay used to switch inducer speed
and gas valve stage. Closes or opens the relay based on
controller’s DC output to the SC30.
Relay closes at approximately 5.3 VDC input
Relay opens at approximately 4.7 VDC input
3) Provides an adjustable timer SC30 (0-30 sec) or xed time,
SC30-XXX: specied in 15 second increments (beginning with
45 seconds - 045) and adjustable VDC (5-15 VDC) output to
the modulating gas valve on startup (powering of SC30). The
feature eliminates problems associated with lighting the burner
at its lowest gas input.
Adjustment potentiometers:
R18 0-30 second timer (SC30 only)
R22 5-15 VDC output voltage (All)
© 2012 Maxitrol
© 2012 Maxitrol