Product Overview

n

n

n


The track mounted SC11 converts a controllers
DC output signal of 4-20 mA or 0-10 V to a 0-20 V
DC signal used to control Selectra valves. Toggling
between 4-20 mA or 0-10 V is achieved with an on-
board 3-position DIP switch: 4-20 mA - all positions on;
0-10 V - all positions off.
  
SC11
4 - 20 mA or
0 - 10 V
0 - 20V DC
Modulator and modulator-regulator valves are available
up to 5 psi (350 mbar) inlet pressure, 30,000 CFH (850
m
3
/h) maximum, and pipe sizes from 3/8” to 4”. (For
additional valve information see Bulletin M_MR.MT.EN,
or consult your Maxitrol sales representative.)
:
0 - 20 VDC. Maximum Load: 1.8 A

-40° to 158°F (-40° to 70°C)

24V AC, 20 VA* (50/60 Hz) transformer.
*VA Dependent on number of valves controlled.
(Maximum Load: 1.8 A)
No grounded secondary.



Maxitrol Company
23555 Telegraph Rd., P.O. Box 2230
Southeld, MI 48037-2230 U.S.A.
www.maxitrol.com
© 2007 Maxitrol Company,
All Rights Reserved.
SC11_AM_MS_EN_07.2007

To Avoid Internal Damage to the SC11 Signal
Conditioner Follow These Guidelines.
1. Transformer secondary must not be grounded
in any portion of the circuit external to the SC11
signal conditioner. A separate, independent
transformer is recommended.
2. Multiple SC11 signal conditioners controlled by
a signal source with common outputs (termi-
nals 5 & 6) require separate transformers for
each SC11 signal conditioner.
3. Multiple SC11 signal conditioners powered
by a single transformer require independent
signal inputs (terminals 5 & 6) to each SC11
signal conditioner.
ACTUAL SIZE SHOWN
DIMENSIONS: 3.10" W x 3.00" H x 1.75" D