NOTE: If vent limiting device is not used, regulator vent must be piped in accordance with government and local codes and
regulations.
RV12L, RV20L
Integral vent limiting orice with dust cap standard.
RV20VL
Integral vent limiting orice with dust cap standard or use 11A08 threaded sleeve nut and run vent line as per code.
RV47
Must order: “L” sufx - Integral vent limiting orice, includes dust cap; or “D” sufx - integral ball-check limiting device, includes
dust cap.
RV48
1/8” NPT vent tap. Optional 12A04 or 12A06 vent limiter. Optional 13A09 dust cap. Optional 10A16-2 or 10A16-3 plastic
thread protector.
RV48L
Integral vent limiting orice.
RV52, RV53, RV61
1/8” NPT vent tap. Optional 12A04 or 12A06 vent limiter or 13A15 vent protector.
RV81
3/8” NPT vent tap. Optional 12A34 vent limiter or 13A15-5 vent protector.
RV91 (2 1/2” pipe size)
1/4” NPT vent tap. Optional 13A15 vent protector. Vent limiter not approved for this model.
RV91 (2” pipe size)
1/2” NPT vent tap. 2” pipe size. Optional 13A25 vent protector. Vent limiter not approved for this model.
RV111, RV131
3/4” NPT vent tap. Vent limiter not approved for these models.
210D
3/8” NPT vent tap. Optional 13A15-5 vent protector. Vent limiter not approved for this model.
210E
1/2” NPT vent tap. Optional 13A25 vent protector. Vent limiter not approved for this model.
210G, 210J
3/4” NPT vent tap. Vent limiter not approved for these models.
220D, 220E, 220G, 220J
Pilot regulator is equipped with 12A06 vent limiting orice, separate vent line is not required.
325-3, 325-3L
1/8” NPT vent tap. Optional 12A09 vent limiting device or 13A15 vent protector.
325-5, 325-5L
3/8” NPT vent tap. Optional 12A39 vent limiting device or 13A15-5 vent protector.
325-7A, 325-7AL
1/2” NPT vent tap. Optional 12A49 vent limiting device or 13A25 vent protector.
325-9, 325-9L
1/2” NPT vent tap. Optional 12A49 vent limiting device or 13A25 vent protector.
R400(S), R500(S), R600(S)
1/8’ NPT vent tap. Optional 12A04 vent limiting device.
OPD47
Integral vent limiting orice, includes dust cap.
OPD48, OPD600
1/8” NPT vent tap. Optional 12A09 vent limiting device or 13A15 vent protector.
OPD210D
3/8” NPT vent tap. Optional 12A39 vent limiting device or 13A15-5 vent protector.
OPD210E
1/2” NPT vent tap. Optional 12A49 vent limiting device or 13A25 vent protector.
NOTICE
Maxitrol vent limiting devices eliminate the need to run vent piping to the outside. Vent limiting devices are designed for
use indoors and in spaces where limiting the amount of gas escapement due to diaphragm failure is critical. Vent limiting
devices should not be used outdoors if they are exposed to the environment. Vent protectors are available for all outdoor
applications to ensure proper vent protection.
CHOOSING A VENT ACCESSORY