Brochure

DRAFT 09.18.2013
42
Pipe Sizes ..................................... 3/8” thru 1” threaded connections with NPT or ISO7-1 threads.
Housing Material ......................... SR400, SR500, SR600: aluminum.
Mounting ..................................... Mount in an upright position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance
with Maxitrol Safety Warning Instructions (see SELMMRSR_MI_EN.FR.ES).
Certications ............................... SR400, SR500, SR600: ANSI Z21.18/CSA 6.3 Gas Appliance Pressure Regulators
(except sufx -2 models).
Gas Types ..................................... Suitable for natural, manufactured, mixed gases, liqueed petroleum gases, and LP gas-air
mixtures.
Maximum Inlet Pressure .............. CSA Certied: 1/2 psi (3.4 kPa)
Maxitrol Tested: 1 psi (6.9 kPa)
Flow Rates .................................... up to 1,000 CFH (28.32 m
3
/h)
Emergency Exposure Limits .......... 2.5 psi (17.2 kPa)
Ambient Temperature Ranges ....... -40 to 175°F (-40 to 79°C)
Minimum Regulation .................... SR400, SR500: 5 CFH; SR600: 60 CFH
NOTE: SR400-2, SR500-2, SR600-2 models are designed primarily for LP gas applications.
NOTE: All models may be powered by a 24 volt AC transformer. When the coil is energized, the appliance is at low re.
When the coil is de-energized, it is high re. Continuous regulation is maintained to hold the electrically set outlet
pressure constant.
An ideal replacement for dual manifold systems, the SR Series
combines gas pressure regulating and ame staging in a single
unit. Applications include direct-red heaters with two speed
fans, hi-lo control for outdoor heaters, LP natural gas switchover
and industrial processing.
SR400
SR SERIES
2 Stage Design
Specications
© 2015, Maxitrol Company. All Rights Reserved.