Brochure
© 2015, Maxitrol Company. All Rights Reserved. © 2015 Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
27
Model
Pipe
Size
Inlet
Pressure
Outlet Pressure - inches w.c. (kPa)
2.0
(0.5)
4.0
(1.0)
6.0
(1.5)
9.0
(2.25)
12
(3.0)
16
(4.0)
20
(5.0)
24
(6.0)
28
(7.0)
210J 4” x 4”
8.0” w.c.
20800
(589)
17000
(481)
12000
(339)
--- --- --- --- --- ---
0.5 psi
29500
(835)
27000
(764)
24000
(680)
19000
(538)
--- --- --- --- ---
0.75 psi
32000
(906)
35000
(991)
33000
(934)
29420
(833)
25500
(722)
19000
(538)
--- --- ---
1 psi
32000
(906)
40000
(1132)
40000
(1132)
37000
(1048)
34000
(963)
29420
(833)
24000
(680)
17000
(481)
---
1.5 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
47000
(1331)
43350
(1227)
39700
(1124)
36000
(1019)
31800
(900)
2 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
48000
(1359)
50000
(1416)
50000
(1416)
48000
(1359)
45000
(1274)
3 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
48000
(1359)
50000
(1416)
50000
(1416)
50000
(1416)
50000
(1416)
5 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
48000
(1359)
50000
(1416)
50000
(1416)
50000
(1416)
50000
(1416)
7.5 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
48000
(1359)
50000
(1416)
50000
(1416)
50000
(1416)
50000
(1416)
10 psi
32000
(906)
40000
(1132)
40000
(1132)
48000
(1359)
48000
(1359)
50000
(1416)
50000
(1416)
50000
(1416)
50000
(1416)
NOTE: CSA maximum capacities vary with spring range and pipe size. Please contact Maxitrol directly for CSA maximums.
See pages 58-59 for Regulator Sizing Requirements and Examples.
Capacities expressed in CFH (m
3
/h) @ 0.64 sp gr gas
Capacities
APPLIANCE REGULATORS