Maxitrol’s original straight-thru-ow (STF) design regulators
are non-lockup type regulators for high capacities at low inlet
pressures. The difference between STF design and other type
regulators is the conical valve. The cone principal permits gas to
ow straight through the regulator without changing directions.
Frictional ow resistance is reduced, resulting in greater
capacity. An improved ow pattern provides accurate, sensitive
regulation at extremely low pressure differentials. Typical
applications include residential, commercial, and industrial
gas-red appliances and equipment used on low or medium
pressure gas supplies.
Pipe Sizes .................................1/2” to 3” threaded connections with NPT or ISO7-1 threads. 4” 150lb. ange (RV131 only).
Housing Material .....................RV52, RV53, RV61, RV81, RV91, RV111: aluminum; RV131: cast iron.
Mounting .................................RV52, RV53, RV61 are suitable for multi-positional mounting. If ball check vent limiting
device is installed, mount in an upright position only. RV81, RV91, RV111, RV131, upright
position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance
with Maxitrol Safety Warning Instructions (see GPR_MI_EN.ES or GPR_CSA_MI_EN.FR).
Certications ...........................RV52, RV53, RV61, RV81, RV91, RV111: ANSI Z21.18/CSA6.3 Gas Appliance Pressure
Regulators.
Gas Types .................................Suitable for natural, manufactured, mixed gases, liqueed petroleum gases, and LP gas-air
mixtures.
Maximum Inlet Pressure ..........CSA Certied: RV52, RV53, RV61, RV81, RV91, RV111: 1/2 psi (3.4 kPa)
Maxitrol Tested*: RV52, RV53: 1/2 psi (3.4 kPa)
RV61, RV81, RV91, RV111: 1 psi (6.9 kPa)
RV131: 2 psi (13.8 kPa)
*Do not use if inlet pressure is more than 10 times desired outlet pressure.
Emergency Exposure Limits ......RV52, RV53: 3 psi (21 kPa)
RV61, RV81, RV91, RV111: 5 psi (34 kPa)
RV131: 15 psi (103 kPa)
Gas Containment Limits ........... RV52, RV53: 15 psi (103 kPa)
RV61, RV81, RV91, RV111, RV131: 25 psi (172 kPa)
NOTE: Internal damage may occur when exposed to these pressures.
Ambient Temperature Ranges ...RV52, RV53, RV61, RV81, RV91, RV111: -40° to 205°F (-40° to 96°C)
RV131: -40° to 125°F (-40° to 52°C)
Minimum Regulation ................RV52, RV53: 20 CFH; RV61: 25 CFH; RV81, RV91: 50 CFH; RV111, RV131: 250 CFH.
Expressed in CFH @ 0.64 sp gr gas.
RV SERIES
Straight-Thru-Flow Design
RV81
Specications