Pipe Sizes ..................................... 3/8” to 1” threaded connections with NPT or ISO7-1 threads.
Housing Material ......................... R400(S), R500(S), R600(S): aluminum.
Mounting ..................................... Suitable for multi-positional mounting. If ball check vent limiting device is installed, mount
in an upright position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance
with Maxitrol Safety Warning Instructions (see GPR_MI_EN.ES or GPR_CSA_MI_EN.FR).
Certications ..................................R400(S), R500(S), R600(S): ANSI Z21.18/CSA 6.3 Gas Appliance Pressure Regulators.
Gas Types ........................................ Suitable for natural, manufactured, mixed gases, liqueed petroleum gases, and LP gas-air
mixtures.
Maximum Inlet Pressure .................CSA Certied: R400(S), R500(S), R600(S): 1/2 psi (3.4 kPa)
Maxitrol Tested: R400, R500, R600: 1 psi (6.9 kPa);
R400S, R500S, R600S: 5 psi (34.5 kPa)
Emergency Exposure Limits ............R400, R500, R600: 2 psi (13.8 kPa)
R400S, R500S, R600S: 12.5 psi (86.2)
Ambient Temperature Ranges ........ R400(S), R500(S), R600(S): -40° to 205°F (-40° to 96°C)
Zero Governor Models ...................Please refer to pages 32-37 for RZ model information.
Minimum Regulation .................... Suitable for pilot ow applications. (Circle P) (0.15 CFH NG), None (1.5 CFH NG).
The R & RS series’ double diaphragm balanced valve design
makes it possible to maintain steady outlet pressure control
with widely varying inlet pressures. The regulator is physically
small yet has exceptional capacity characteristics. R & RS series
regulators are intended for use with both main burner and pilot
load applications. They are ideally suited for use with infrared
heaters and pilot lines on large industrial heaters and boilers.
R/RS SERIES
Balanced Valve Design
R400
Specications