User Guide

Timers
The controller features two Timers (Timer 1 and Timer 2) that accumulate
the hours of operation for each Process. Each Process has a Timer 1 and
a Timer 2. The TM02 is required.
Timer 1
Timer 1 logs the hours of operation for a Process. It will log up 999 hours
at which time it will automatically reset to zero. The hours can be user
reset to zero at any time. It also has a programmable alarm setting to
notify the user (by ashing a character in the lower right hand corner of
the display) when the desired accumulated hours for the Process have
been reached. It has a setting range of 1 to 999 hours. The feature is
useful in maintaining maintenance requirements.
Timer 2
Timer 2 logs the hours of operation for a Process. It will log up 999 hours
at which time it will automatically reset to zero. The hours can be user
reset to zero at any time. The feature is useful in maintaining maintenance
requirements.
Diagnostic Menu
Max Proc Temp
This feature limits the maximum temperature for each Process. It has a
range of 60°F (15°C) to 240°F (115°C). It does not allow the Process Set
Point to be set in excess of the Maximum Process Temperature setting.
Min Proc Temp
This feature limits the minimum temperature for all Processes. It has a
range of 60°F (15°C) to 240°F (115°C). It does not allow any Process Set
Point to be set below the Minimum Process Temperature setting.
Calibration
This feature is used to ne-tune a particular application. Calibration
shifts the Bandwidth range up or down from the factory set mean. Each
application is different with variances in burners and appliances. It can be
necessary to change the midpoint of the modulation range to have the
Process Temperature and the actual sensed temperature match.
For sensed temperatures consistently displaying lower than the Set
Point, increase (+) Calibration by number of degrees off. For sensed
temperatures consistently displaying higher than the Set Point, decrease
(-) Calibration by number of degrees off. It is available for each Process
and has a range of –10°F (-5.6°C) to +10°F (5.6°C).
Features
6
© Copyright 2007, Maxitrol Company. All Rights Reserved.