User Guide

Process Menu
Process Set Point
A maximum of (8) Process Set Points are available with a temperature
range of 60°F (15°C) to 240°F (115°C).
The Process Set Point is displayed as “SP.”
Process Set Points not being used can be turned to an “Off” setting.
Process Times (TM02 required)
Any of the (8) Processes can be timed. Each timed Process has a range of
00:00:01 to 23:59:59. The conclusion of a timed Process will immediately
proceed into the next Process. If the last Process of the program is timed,
it will proceed to the selected start position (see Looping Mode, page 7)
after timing out. The letter “T” will be displayed indicating a timed Process.
Press the up or down arrows on the TDM02 to scroll between the screens
showing the Process Set Point and the sensed temperature AND the
sensed temperature with the time remaining in the Process (hh:mm:ss).
Operation Menu
Soft Start
The Soft Start feature controls the initial rate of voltage change to the
modulator. Soft Start operates when switching from a lower Process
temperature to a higher Process temperature. It is designed to slow the
initial input rate to the burner. This feature is available in three settings:
slow, medium, and fast and may be turned off. “Ss” (slow), “Sm” (medium)
or “Sf” (fast) is displayed during the time the Soft Start is active. This feature
is comprehensive to all Set Points.
Max Valve VDC
This feature limits the maximum voltage applied to the modulator. It has a set-
ting range of 7 to 25 VDC. This feature is comprehensive to all Set Points.
Max Ramp VDC
This feature limits the maximum voltage applied to the modulator while
operating in the Ramping mode. It has a setting range of 5 to 24 VDC. This
setting cannot exceed the maximum voltage output setting. This feature is
comprehensive to all Set Points.
Total Bandwidth
This feature determines the amount of temp. change required to drive the
modulator from the minimum re setting to the maximum re setting and
vice versa. This feature is used to eliminate pulsating or hunting due to an
oversensitive application. Increase the Bandwidth if a pulsating or hunting
condition exists for an extended period of time after a Set Point change.
The feature has a range of 5°F (2.8°C) to 15°F (8.3°C). Total Bandwidth is
comprehensive to all Set Points.
Features
4