User Guide
Valve Adjustments
30
M411, 511, 611 Valve
High Fire Adjustment:
1 Short the sensor connection at the amplier. This drives the valve to
a continuous high re condition.
2 Adjust the pressure regulator to obtain the desired manifold pressure
(7˝ w.c. maximum).
3 Remove the short to the amplier sensor connection.
Low Fire Adjustment:
1 Remove a sensor wire from amplier terminal. This drives the valve
to a continuous low re condition.
2 Remove bypass seal cap (A, Figure 2), and turn adjusting screw (B,
Figure 2) to desired low re adjustment. (Clockwise rotation reduces
minimum ow rate.)
3 Replace cap (A, Figure 2), and reconnect sensor wire to amplier.
NOTE: See Bulletin M.MR_MT_EN for additional M/MR valve information.
© Copyright 2007, Maxitrol Company. All Rights Reserved.
A
B
Figure 2.