User Guide

Valve Adjustments
29
NOTE: Low re adjustment should be checked whenever the high re
adjustment is changed.
MR212 Valve
High Fire Adjustment:
1 Short the sensor connection at the amplier. This drives the valve to
continuous high re condition.
2 Remove seal cap (A, Figure 1), and turn regulator pressure adjusting
screw to obtain desired manifold pressure. (Clockwise rotation
increases pressure.)
3 Remove the short to the amplier sensor connection.
NOTE: If low re bypass is on maximum, the desired high re outlet pressure
may not be achieved.
Low Fire Adjustment:
1 Remove a sensor wire from amplier terminal. This drives the valve
to a continuous low re condition.
2 Remove cap (B, Figure 1), and loosen lock screw (C, Figure 1).
Turn (D, Figure 1) to desired low re adjustment. (Clockwise rotation
reduces minimum ow rate.)
3 Tighten set screw (C, Figure 1), replace cap (B, Figure 1) and
reconnect sensor wire to amplier.
© Copyright 2007, Maxitrol Company. All Rights Reserved.
Figure 1.