User Guide

Preliminary Circuit Analysis
27
In order to diagnose the system it is necessary to determine certain
values. It is helpful to have a volt/ohm multimeter and a xed or variable
resistance between 1100 and 1300 ohms.
Modulation Function:
If sensed (displayed) process temperature is less than 70ºF, perform
step 1 below, otherwise continue to step 2.
1 Disconnect the sensor wires going to the amplier and replace with
means to obtain a resistance value falling somewhere within the
controllers programmed range.
NOTE: “Max Proc Temp” and “Min Proc Temp” settings are located in the
Diagnostic Menu in the MP2.
R ohms Proc T displayed (approx.)
1100 78
1200 125
1300 172
2 Connect a DC voltmeter to the modulating gas valve or the
modulating gas valve amplier terminals. DO NOT disconnect
existing wiring. OR Activate the MP2’s “Monitor” function located in
the Diagnostic Menu to display the voltage output to the modulating
gas valve.
3 Program the temperature “set point” to 10ºF below the displayed
“process temperature”. The DC volts should read no more than 2
VDC.
4 Program the temperature set point to 10º above the displayed
“process temperature”. The DC volts should read at a minimum 15
VDC or the programmed “Max Value VDC” setting located in the
Operation Menu, whichever is less.
NOTE: Controls programmed with a large Offset Temp or Calibration setting
may fail step 3 or 4 due to one or both of the programmed settings. Re-run
the failed test with a 20ºF set point temperature differential or zero the Offset
Temp and Calibration settings. Make note of the settings prior to zeroing and
return them to their original setting after test.
© Copyright 2007, Maxitrol Company. All Rights Reserved.