User Guide
Preliminary Circuit Analysis
27
In order to diagnose the system it is necessary to determine certain
values. It is helpful to have a volt/ohm multimeter and a xed or variable
resistance between 1100 and 1300 ohms.
Modulation Function:
If sensed (displayed) process temperature is less than 70ºF, perform
step 1 below, otherwise continue to step 2.
1 Disconnect the sensor wires going to the amplier and replace with
means to obtain a resistance value falling somewhere within the
controllers programmed range.
NOTE: “Max Proc Temp” and “Min Proc Temp” settings are located in the
Diagnostic Menu in the MP2.
R ohms Proc T displayed (approx.)
1100 78
1200 125
1300 172
2 Connect a DC voltmeter to the modulating gas valve or the
modulating gas valve amplier terminals. DO NOT disconnect
existing wiring. OR Activate the MP2’s “Monitor” function located in
the Diagnostic Menu to display the voltage output to the modulating
gas valve.
3 Program the temperature “set point” to 10ºF below the displayed
“process temperature”. The DC volts should read no more than 2
VDC.
4 Program the temperature set point to 10º above the displayed
“process temperature”. The DC volts should read at a minimum 15
VDC or the programmed “Max Value VDC” setting located in the
Operation Menu, whichever is less.
NOTE: Controls programmed with a large Offset Temp or Calibration setting
may fail step 3 or 4 due to one or both of the programmed settings. Re-run
the failed test with a 20ºF set point temperature differential or zero the Offset
Temp and Calibration settings. Make note of the settings prior to zeroing and
return them to their original setting after test.
© Copyright 2007, Maxitrol Company. All Rights Reserved.










