User Guide

17
Operation
MP2 Process Control System w/
TM02 Multifunctional Timer Control
Switching to the Next Programmed Process
Timed processes
Nothing is required. The MP2 System will immediately proceed to the
next programmed Process after timing out.
NOTE: If the last Process of a program is timed, it will proceed either to the
“READY” position or to the First Process. By selecting the First Process in
the LOOPING Mode menu, the MP2 can be programmed into a continuous
program loop (see page 7, LOOPING Mode).
Untimed (Manual) Processes
An untimed Process will remain in the Process indenitely until Button
1 is pushed and released or TB1 is momentarily latched. Pushing and
releasing Button 1 or the momentary latching of the TB1 will cause the MP2
System to proceed to the next Process. If the last Process of a program
is untimed, pushing and releasing Button 1 or the momentary latching of
TB1 will cause the MP2 system to proceed to the selected program start
position. Multiple contacts used to switch untimed Processes are to be
wired in parallel.
Aborting a Timed Process
Push and release Button 1 or momentarily latch TB1 twice within a 10
second period or latch and hold continuously for 10 seconds.
Connecting Indicator Relays
Process 1 thru 7 indicators use a corresponding pair of terminals, labeled
Relay (1 - 7), on the TM02. The Program indicator uses a corresponding
terminal labeled Relay 8. Wire each indicator (LED, relay coil, etc.) 24
VDC 2 W maximum directly to the desired corresponding terminal. See
gure A, page 18. Note polarity where applicable.
© Copyright 2007, Maxitrol Company. All Rights Reserved.