User Guide

14
Programming the MP2
Ramping
2 Scroll to Ramping, press
ENT
.
3 Ramping Process #, scroll to Set Point #, press
ENT
.
4 Rmp Rate Proc #, set Ramp Rate (Off, 60 to 900 Deg/Hr),press
ENT
.
5 **Stored** will ash 4 times to conrm entry.
6 Repeat steps 2 through 7 for Set Points #(2 - 8).
Timers (TM02 required)
2 Scroll to Timers, press
ENT
.
3 Timer Process #, scroll to Set Point #, press
ENT
.
4 Timer Process #, scroll to Timer 1 or Timer 2, press
ENT
.
5 Timer 1: T1 Proc #, scroll to View Hours, Clear Hours
or Set Alarm Hours, press
ENT
.
View hours
a XXX Hours
Clear hours
b Are You Sure? scroll for Y or N, press
ENT
.
c If Y, Timer1 Hrs Clear ashes to conrm entry.
Set alarm hours
d T1 Proc # Alarm, scroll to set hrs, press
ENT
.
e Set Timer1 Alarm ashes to conrm entry.
6 Timer 1: T2 Proc #, scroll to View Hours or
Clear Hours, press
ENT
.
View hours
a XXX Hours
Clear hours
b Are You Sure? scroll
for Y or N, press
ENT
.
c If Y, Timer2 Hrs Clear ashes to conrm entry.
7 Repeat steps 2 through 6 for Set Points #(2 - 8).
© Copyright 2007, Maxitrol Company. All Rights Reserved.