User Guide

13
Programming the MP2
Operation Menu programming:
1 Scroll to the Operation Menu, press
ENT
.
Soft Start
2 Scroll
to Soft Start and press
ENT
.
3 Soft Start, scroll to Off, Slow, Medium or Fast, press
ENT
.
4 **Stored** will ash 4 times to conrm entry.
Max Valve VDC
2 Scroll to Max Valve VDC, press
ENT
.
3 Max Valve VDC, set voltage value (7 V to 25 V), press
ENT
.
4 **Stored** will ash 4 times to conrm entry.
Max Ramp VDC
2 Scroll to Max Ramp VDC, press
ENT
.
3 Max Ramp VDC, set voltage value (5 V to 24 V), press
ENT
.
4 **Stored** will ash 4 times to conrm entry.
NOTE: Voltage can not be set greater than Max Valve VDC.
Total Bandwidth
2 Scroll to Total Bandwidth, press
ENT
.
3 Total Bandwidth, set Bandwidth (5°F (-2.8°C) to 15°F (8.3°C)),
press
ENT
.
4 **Stored** will ash 4 times to conrm entry.
Offset
2 Scroll to Offset Temp, press
ENT
.
3 Offset Temp Process #, scroll to Set Point #, press
ENT
.
4 Offset Temp Process #, set Offset (-10°F (-5.6°C) to 10°F
(5.6°C)), press
ENT
.
5 **Stored** will ash 4 times to conrm entry.
6 Repeat steps 2 through 5 for Set Points #(2 - 8).