Install Instructions
Valve Adjustments
(
See bulletin MT2035 for additional M/MR valve information
)
NOTE: NOTE:
NOTE: NOTE:
NOTE: Low Fire Adjustment should be checked whenever High Fire Adjustment is changed.
High Fire Adjustments:High Fire Adjustments:
High Fire Adjustments:High Fire Adjustments:
High Fire Adjustments:
Rotate selector dial to maximum temperature setting.
NOTE:
Voltage to the valve must be at least 18VDC.
M411, M420, M511, M520, M611, and M620 -
Adjust separate pressure regulator to obtain desired manifold pressure.
M451, M551, and M651 -
Adjust separate pressure regulator to obtain desired manifold pressure.
MR212D, E, and G - MR251D, E, and G - (
see figure 1
)
Remove cap (A) and turn regulator pressure adjusting screw to obtain
desired manifold pressure. Clockwise rotation increases pressure.
BB
BB
B
M411, M420, M511, M520, M611, and M620 - (
see figure 2
)
Remove by-pass cap (A) and turn screw (B) using small screwdriver to desired
low fire adjustment.
NOTE: Clockwise screw rotation reduces flow rate. Do not overtighten.
Low Fire Adjustments:Low Fire Adjustments:
Low Fire Adjustments:Low Fire Adjustments:
Low Fire Adjustments: Disconnect a wire from M or MR valve terminal
block.
NOTE: Be careful not to allow wire to come into contact with any other part.
MR212D, E, and G - (
see figure 1
)
Remove cap (B) from by-pass metering valve and loosen lock screw (C).
Turn adjusting screw (D) to desired low fire adjustment.
M451, M551, M651 - MR251D, E, G, - (
see figure
3
)
Remove cover plate (A). Using minimum adjusting screw (B), set manifold
pressure to manufacturer's specifications.
f
igure 1
f
igure 2
f
igure 3
AA
AA
A
AA
AA
A
BB
BB
B
7