Submittal
© 2017, Maxitrol Company. All Rights Reserved.
50
Pipe Sizes .................................... 3/8” thru 2” threaded connections with NPT or ISO7-1 threads.
Housing Material ........................ All models: aluminum.
Mounting All models with the exception of 325-7AL210D and 325-9L210E are suitable for
multi-positional mounting. 325-7AL210D and 325-9L210E are to be mounted in a
horizontal upright position only. If ball check vent limiting device is installed, mount in an
upright position only.
...................................................... NOTE: Line pressure regulators with separate overpressure protection
devices are factory preassembled and supplied to the eld as a unit. All Maxitrol gas pressure
regulators should be installed and operated in accordance with Maxitrol Safety Warning
Instructions (see LPROPD_MI_EN.FR).
Certications ................................ All models: ANSI Z21.80/CSA 6.22 Line Pressure Regulators
Gas Types .................................... Suitable for natural, manufactured, mixed gases, liqueed petroleum gases, and LP gas-air
mixtures.
Rated Inlet Pressure .................... 5 psi (34.5 kPa)
Maxitrol Tested ........................... 10 psi (69 kPa)
With 12A09, 12A39, or 12A49 Vent Limiter Installed
Natural: 5 psi (34.5 kPa); LP: 2 psi (13.8 kPa)
Emergency Exposure Limits ......... 65 psi (450 kPa) (inlet side only)
Maximum Individual Load/
Capacity ...................................... 325-3L47 (3/8”, 1/2”) (w/OPD 47 attached).................................. 125,000 Btu/h
325-3L48 (1/2”) (w/OPD 48 attached)........................................... 200,000 Btu/h
325-5L48 (1/2”) (w/OPD 48 attached)............................................235,000 Btu/h
325-5L48 (3/4”) (w/OPD 48 attached)............................................320,000 Btu/h
325-5L600 (3/4”) (w/OPD 600 attached)........................................425,000 Btu/h
325-5L600 (1”) (w/OPD 600 attached)...........................................465,000 Btu/h
325-7AL210D (1 1/4”, 1 1/2”) (w/OPD 210D attached) ..............1,250,000 Btu/h
325-9L210E (1 1/2”, 2”) (w/OPD210E attached)..........................2,250,000 Btu/h
Ambient Temperature Ranges ...... -40 to 205°F (-40 to 96°C)
Minimum Regulation ................... Suitable for pilot ow applications. (Circle P) (0.15 CFH NG).
Maxitrol’s 325-L Series line pressure regulators with OPDs
are for use on piping systems up to 5 psi. The regulator
reduces pounds pressure to a level within the appliance
or equipment’s operating supply range. The line regulator
is located upstream of equipment already tted with an
appliance regulator.
325-3L47
Specications
325-L SERIES
Lever Acting Design with OPDs
for 5 psi Piping Systems