Manual

LEVER ACTING DESIGN
GAS APPLIANCE PRESSURE REGULATOR
Upright
When vented to the outdoors
the 325 Series is suitable for
multi-poise mounting. When
using the vent limiting
device, the regulator (325-3,
325-5A) must be mounted in
a horizontal upright position.
Install the regulator properly
with gas flowing as indicated
by the arrow on the casting
(also see the Safety Warning
Instructions bulletin).
325-3*, 325-5A*, 325-7
Pipe sizes from 3/8” to 1-1/2”
CSA 6.3 and ANSI Z21.18
Design Certified - 325-3, 325-5A
Maximum Inlet Pressure:
ANSI Z21.18 Certified - 325-3, 325-5A .....2psi (140 mbar),
Maxitrol-tested: all models......................10 psi ( 690 mbar)
With 12A09 or 12A39:
Max. inlet pressure (LP)........................2 psi (140 mbar)
Max. inlet pressure (natural)...................5 psi (345 mbar)
Emergency Exposure Limits
All models (inlet side only).......................65 psi (4.5 bar)
Maximum Individual Load
Largest single appliance served by the regulator
325-3......................................................100,000 Btu/hr
325-5A....................................................250,000 Btu/hr
325-7......................................................900,000 Btu/hr
Capacity:
Total load of all appliances combined
325-3 (3/8”, 1/2”)......................................150,000 Btu/hr
325-5A (1/2”, 3/4”, 1”)..................................300,000 Btu/hr
325-7 (1-1/4”, 1-1/2”)..............................1,000,000 Btu/hr
Ambient Temperature Limits
All models...............................-40° to 205°F (-40° to 96°C)
DVGW...........................................32° to 140°F (0° to 60°C)
EN................................................5° to 176°F (-15° to 80°C)
Vent Pipe Connection Size:
325-3 ..............................................................1/8" NPT
325-5A.............................................................3/8" NPT
325-7................................................................1/2" NPT
Gases: Suitable for application in natural, manufactured, mixed
gases, liquefied petroleum gases, and LP gas-air mixture piping
systems.
NOTE: All Maxitrol gas appliance regulators must be installed
and operated in accordance with Maxitrol's 'Safety Warning'
bulletin.
* Design Certified - 325-3, 325-5A
5 psi (345 mbar)
© 2008, Maxitrol Company, All Rights Reserved
1