Instruction manual
14
EN
4.2. Quick Start ATy
STEP 4
Clip for
storage of
the
emergency
handle
STEP 3
QUICK START
EN
541 994 D - 02/14 - EN
ATyS t
Motorised Source Changeover Switch
Automatic Transfer Switching Equipment
www.socomec.com
To download, brochures, catalogues and technical manuals:
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
Non contractual document.
Sub
j
ect to chan
g
e without notice.
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■ Packaging and contents are in good condition.
■ The product reference corresponds to the order.
■ Contents should include:
Qty 1 x ATyS t
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■ This product must always be installed and commissioned
by qualified and approved personnel.
■ Maintenance and servicing operations should be
performed by trained and authorised personnel.
■ Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■ Always use an appropriate voltage detection device to
confirm the absence of voltage.
■ Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
■ In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
■ Bridging bars and connection kits.
■ Control voltage transformer (400Vac -> 230Vac).
■ DC power supply (12/24Vdc -> 230Vac).
■ Mounting spacers to raise the product x 10mm.
■ Phase barriers.
■ Terminal shrouds.
■ Terminal screens.
■ Auxiliary contacts (Additional).
■ Padlocking in 3 positions (I - O - II).
■ Lockout accessories (RONIS - EL 11 AP).
■ Door escutcheon frame.
■ ATyS D10 Interface (remote display).
■ Voltage sensing kit.
■ Sealable cover.
■ RJ45 cable for ATyS D10 => ATyS t
For further details refer to the product instruction manual
under chapter "Spares and Accessories"
STEP 1
Cabinet / Back
Plate Installation
STEP 3
COMMAND /
CONTROL terminal
connections
STEP 2
Power Terminal
Connections
STEP 4
Power SUPPLY and
ATS Controller
Terminal
Connections
STEP 5
CHECK
STEP 6
PROGRAMMING
Installation and Commissioning
STEP 7A
AUT Mode
(Automatic Control)
STEP 7C
Manual Mode
STEP 7B
AUT Mode
(Remote Control)
STEP 7D
Padlocking Mode
STEP 4
ATS Voltage Sensing
Input
Source supply I
S I - Phase 1
S I - Phase 2
S I - Phase 3
600 VAC (ph-ph) max
S I - Neutral
332 VAC (ph-n) max
ATS Voltage Sensing
Input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
600 VAC (ph-ph) max
S II - Neutral
332 VAC (ph-n) max
ATS Module
Control Inputs
(Fixed)
ATS Module
Output Contact
(Product available)
Remote interface
RJ45 - to ATyS D10
Power 208-277V~ +/-20%
To D10
64B 63B
417 416 415 414 413
Power 208-277V~ +/-20%
Power Supply, Sensing and Control wiring (ATS Controller)
Connect the product with a cable of section of 1,5 to 2,5 mm
2
.
Screw M3 - Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
ATS Power Supply
Power supply II - L
Power supply II - N
50/60 Hz
ATS Power Supply
Power supply I - L
Power supply I - N
50/60 Hz
Recommanded to use SOCOMEC
Voltage Sensing Kit
(refer to ATyS t
accessories
for details)