1. MANUAL Mode LED indication.
(Yellow steady light when in Manual Mode).
2. AUTO Mode LED indication
Green steady light when in Auto mode with
no timers running.
Green flashing light when in Auto with timers
running in the background.
3. REMOTE CONTROL Mode LED indication.
Yellow steady light when in remote control
mode.
Remote control mode is achieved with the
Auto/Manu selector switched to Auto and
terminals 312 closed with terminal 317.
Remote control orders are received through
closing 314 to 316 with 317.
4. Switch 1 LED position indication.
(Green when in position 1).
5. Source supply I availability LED indication.
(Green when supply I voltage is within the
set limits).
6. Zero position LED indication.
(Yellow when in position 0).
7. Switch 2 LED position indication.
(Green when in position 2).
8. Source supply II availability LED indication.
(Green when supply II voltage is within the
set limits).
9. Sealing screw location 1 for use with sealing
cover (Available as an accessory)
10. Potentiometer 1: Supply FAILURE Time (FT)
Adjustable from 0 to 60 seconds.
11. Potentiometer 2: Supply RETURN Time (RT)
Adjustable from 0 to 60 minutes.
12. READY LED indication
Green steady light : Product in AUTO,
Watchdog OK, Product Available to
changeover.
Green flashing: Settings displayed not
saved or have been changed since last
saved.
(Press PROG OK button in manual mode to
save or revert to last saved settings).
13. Sealing screw location 2 for use with the
sealing cover.
14. FAULT LED indication. (Red steady light in
case of an ATS controller internal fault).
15. Configuration dip switches :
(4 dip switches with 2 positions in each
A to H).
16. PROG OK: Configuration save push button.
(ATTN: Active in Manual Mode ONLY).
Press briefly to confirm and save all set
configuration settings.
Hold pressed for 2 seconds to set the
network supply voltage and frequency by
Auto Configuration.
This is to be followed by pressing briefly to
save the set value configured.
17. Green LED Indication: Power
18. Red LED Indication: Product Unavailable /
Manual Mode / Fault Condition
19. Auto / Manual mode selector switch
(Key version available as an option)
20. Padlocking facility
(Up to 3 padlocks of dia. 4 – 8mm)
21. Emergency manual operation shaft location
(Accessible only in manual mode)
22. Switch position indication window:
I (On switch I) O (Off) II (On switch II).
1920
21
22
5
4
2
1
3
13
17
18
14
15
12
16
896 7 10 11
Ensure that the emergency handle is
not inserted in the product and turn
the mode selector to the AUT position.
LED “Power” Green: ON
LED Manuel/Default: OFF
STEP 7A
AUT Mode
STEP 7B
AUT Mode
To enable control, close contact 312 with 317.
For contactor logic bridge contact 316 with 317.
To operate: close the contact corresponding to
the desired position.
To force the product to 0 position “OFF” bridge
contact 313 with 317.
maintened
order I
position I
order 0
position 0
order II
position II
Contactor logicImpulse logic
STEP 7D
Padlocking Mode
(as standard : in position O)
STEP 7C
Manual Mode
90°
90°
III
0
AUT
AUT
REMOTE CONTROL
AUT
REMOTE CONTROL
AUT
REMOTE CONTROL