Instruction manual

12
EN

STEP 6
Programming the ATyS t
Dip Switch Setting Options
SET the 4 Dip Switches using a small screw driver. Possible variants vary from positions “A to
H” as described in the table below. For convenience, the position functions are also described
on the front of the ATS controller adjacent to the dip switches.
Note: The READY LED will flash green as soon as settings are changed and until the new settings
have been saved by pressing the PROG OK button momentarily.
PROG
OK
READY
A
:
B
:
C
:
D
:
O
TE CONTR
O
R
Dip Switch Setting Options
Dipswitch 1
A / B
A Three Phase Network
B Single Phase Network
(Attn : Dipswitch 2 is inactive in this position)
Dipswitch 2
C / D
C Three Phase 4 wire Network (Including Neutral)
(Allows to detect a loss of neutral for unbalanced loads)
D Three Phase 3 wire Network (Without Neutral)
Dipswitch 3
E / F
E Without a time delay in Zero Position (DBT = 0 sec)
F Zero position time delay set to 2s (DBT = 2 sec)
Dipswitch 4
G / H
G Threshold Delta U : 10% / Delta F : 5%
H Threshold Delta U : 20% / Delta F : 10%
Potentiometer Setting Options
SET the 2 potentiometers using a small screw driver paying attention to the arrow indicating
the position. There are a total of 14 positions for which the specific settings are described in
the table below.
Note: The READY LED will flash green as soon as settings are changed and until the new settings
have been saved by pressing the PROG OK button momentarily.
0
1
5
10
20
60
0
1
5
10
20
60
Functional Description
Potentiometer 1 FT Supply Source Failure time : 0 to 60s
Potentiometer 2 RT Supply Source Return Time : 0 to 60 min
Position Setting Identification
Pos. 1 2 3 4 5 6 7 8 9 10 11 12 13 14
FT (sec) 0123458101520304050 60
RT (min) 0123458101520304050 60
Auto Configuration of Mains Voltage and Frequency
The ATyS t includes an “Auto Configuration” feature to detect the mains voltage and frequency
nominal values, phase rotation and neutral position and saves them in the ATS controller.
Note: Before configuring the nominal values ensure that the product is properly wired, verified
and ready for commissioning. It is imperative that the network supply is available and that the
wiring to the ATyS t voltage sensing terminals 103 – 106 and 203 – 206 has been done. It is
preferable to use the ATyS sensing kit that may be provided as an accessory.


!"#"$"%$&'*+
READY LED will flash green as soon as settings are measured and until these settings have been
saved by pressing the PROG OK button a second time momentarily. (Refer to STEP 4).
PROG
OK
AUT
READY
REMOTE CONTROL
A:
B:
C:
D:
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Saving the configured values
To SAVE the recorded setting configuration press the PROG OK button momentarily: <60ms.
Note: The flashing READY LED goes off once the values are saved in the ATS controller.
PROG
OK
AUT
READY
REMOTE CONTROL
A:
B:
C:
D:
Putting the ATyS t into Auto Operation
After following Steps 1 to 4, and once ready to put the ATyS t into AUTO operation turn the mode
selector switch to Auto.
Note: When the product is powered and properly configured, after switching the product from
Manual Mode to Auto Mode the READY light should be a steady green light.
PROG
OK
AUT
READY
0
1
5
10
20
60
0
1
5
10
20
60
G: U
10% F
5%
H:
U
20% F
10%
E:
F:
REMOTE CONTROL
A: 3 Ph
B: 1 Ph
C: Neutral
D: Neutral
PROG
OK
AUT
READY
0
1
5
10
20
60
0
1
5
10
20
60
G: U
10% F
5%
H:
U
20% F
10%
E:
F:
REMOTE CONTROL
A: 3 Ph
B: 1 Ph
C: Neutral
D: Neutral
WARNING
Depending on the state of the ATyS t the ATS automation may change the switch
position as soon as the mode selector is switched to AUT. This is a normal operation.
WARNING
As a safety measure
the READY LED will flash when any of the
settings shown on the controller are different
to those that are saved. To return to the steady
READY LED revert to the saved setting values
or save the displayed value by pressing the
PROG OK button briefly. (This is intended as
a visual alarm in case one has changed the
configuration settings but has not yet saved
the new values in the product).
For added security the ATyS t may be
equipped with a sealable cover so as to limit
the access to configuration settings. Refer
to the product accessory section for details.
Note: Ensure that the ATyS t is
in “Manual Mode”, powered and
with at least one network supply
available.
The ATyS t is programmed after
wiring verification tests through
the front of the ATS Controller
in 5 steps:
Check
Whilst in manual mode, check the
wiring and if ok power up the
product.
LED “Power” Green: ON
LED Manuel/Fault Red: ON
STEP 5
Power 208-277V~
Power 208-277V~
+
+/-20%
+/-20%
