Table 35. MFR_CHANNEL_CONFIG (E4h)
Table 36. Fault-Monitoring States
*For proper sequencing, the SELECT bits in MFR_PSEN_CONFIG must be set to 000.
Note: Device response to faults is determined by the configuration of MFR_FAULT_RESPONSE.
BIT NAME MEANING
15:12 0
Thesebitsalwaysreturna0.
11:8 SEQ_GENERATE
These bits determine which SEQ signature the channel should generate after crossing the
POWER_GOOD_ONlevel:
0000 Disabled 1000 Signature8
0001 Signature1 1001 Signature9
0010 Signature2 1010 Signature10
0011 Signature3 1011 Signature11
0100 Signature4 1100 Signature12
0101 Signature5 1101 Signature13
0110 Signature6 1110 Signature14
0111 Signature7 1111 Signature15
7:6 0 Thesebitsalwaysreturna0.
5:0 SELECT[5:0]
ThesebitsselectthefunctionoftheRSn/GPInpins:
SELECT[5:0] SELECTEDCHANNELFUNCTION
010000(10h) Sequencing+voltagemonitoring(onlyvalidforPAGES0–11)*
100000(20h) Voltagemonitoring(nosequencing)
100010(22h) Currentmonitoring
100001(21h) Voltagereadonly
100011(23h) Currentreadonly
110000(30h) General-purposeinputactivelow
110100(34h) General-purposeinputactivehigh
000000(00h) Disabled
FAULT
REQUIRED DEVICE CONFIGURATION
FOR ACTIVE MONITORING
WHEN MONITORED
Overvoltage
•
Voltagemonitoringenabled
(SELECT[5:0]=10hor20hinMFR_CHANNEL_CONFIG)
Continuous monitoring.
Undervoltage
•
Voltagemonitoringenabled
(SELECT[5:0]=10hor20hinMFR_CHANNEL_CONFIG)
Stopsmonitoringwhilethepowersupplyis
off;startsmonitoringwhenvoltageexceeds
thePOWER_GOOD_ONlevel.
Overcurrent
•
Currentmonitoringenabled
(SELECT[5:0]=22hinMFR_CHANNEL_CONFIG)
Continuous monitoring.
Power-UpTime
• Sequencingenabled
(SELECT[5:0]=10hinMFR_CHANNEL_CONFIG)
Monitored only during power-on sequence.
Overtemperature
• Temperature sensor enabled
(ENABLE=1inMFR_TEMP_SENSOR_CONFIG)
Continuous monitoring.