Device Identification Commands 
CAPABILITY 
Reference: 
Standard Command 
Lockable: 
N/A 
Command Code: 
0x19 
Format: 
Bit field 
Data Bytes: 
1 
Units: 
N/A 
Transfer: 
Read Byte 
Factory Value: 
0xA0 
Description/Notes: 
See Section 11.12 of the PMBus Specification Part II. 
PMBUS_REVISION 
Reference: 
Standard Command 
Lockable: 
N/A 
Command Code: 
0x98 
Format: 
Bit field 
Data Bytes: 
1 
Units: 
N/A 
Transfer: 
Read Byte 
Factory Value: 
0x22 (see Description) 
Description/Notes: 
See Section 22.1 of the PMBus Specification Part II. 
Note  that  due to a typographical error in the PMBus Specification version 1.2, wherein bit #4 is 
omitted from the PMBUS_REVISION data byte, the Maxim interpretation is to correct this error and 
include bit #4, placing the Part I Revision level in bits [7:4] and the Part II Revision level in bits [3:0].
e
Bits [7:4] describe the PMBus specification Part I revision level as follows: 
0000  Revision 1.0 
0001  Revision 1.1 
0010  Revision 1.2 
Bits [3:0] describe the PMBus specification Part II revision level as follows: 
0000  Revision 1.0 
0001  Revision 1.1 
0010  Revision 1.2 
MFR_ID 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x99 
Format: 
ASCII string 
Data Bytes: 
8 
Units: 
N/A 
Transfer: 
Read/Write Block 
Factory Value: 
String of 6 spaces (ASCII 0x20) 
Description/Notes: 
See Section 22.2.1 of the PMBus Specification Part II. 
Note that the MAX15303 implements MFR_ID as a fixed-width string, not as part of a shared memory 
space. 
e
  See the PMBus Specification, Part II, draft version 1.3, where this error is corrected to agree with the interpretation 
described here. 