MAX15301 PMBus Command Set User’s Guide 
Rev 1    Page 42 of 53 
SECURITY_LEVEL 
Reference: 
Maxim Specific 
Lockable: 
N/A 
Command Code: 
0xE6 
Format: 
Direct 
Data Bytes: 
1 
Units: 
N/A 
Transfer: 
Read Byte 
Factory Value: 
0x00 
Description/Notes: 
The MAX15301 provides two levels of password protection for all writeable PMBus commands, on a 
per-command basis. The SECURITY_LEVEL command value shows the present security level as follows: 
SECURITY_LEVEL  Description 
0x00  No write access to commands locked by USER_CONF or MANUF_CONF 
0x01  Write access granted to commands locked by USER_CONF 
0x02  Write access granted to commands locked by MANUF_CONF and USER_CONF 
Note that SECURITY_LEVEL is 0 until a value is written to USER_PASSWD  or  MANUF_PASSWD  that 
matches the working-memory value of USER_LOCK or MANUF_LOCK respectively. 
When the working-memory value of USER_LOCK is written to USER_PASSWD, SECURITY_LEVEL is set 
to 1. 
When the working-memory value of MANUF_LOCK is written to MANUF_PASSWD, SECURITY_LEVEL is 
set to 2. 
Writing a “mismatched” (or wrong) value of USER_PASSWD or MANUF_PASSWD causes 
SECURITY_LEVEL to reset to 0. 
The values of USER_LOCK and USER_CONF can only be changed when SECURITY_LEVEL is 1 or 2. 
The values of MANUF_LOCK and MANUF_CONF can only be changed when SECURITY_LEVEL is 2. 