Fault Related Commands 
CLEAR_FAULTS 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x03 
Format: 
N/A 
Data Bytes: 
0 
Units: 
N/A 
Transfer: 
Send Byte 
Factory Value: 
N/A 
Description/Notes: 
See Section 15.1 of the PMBus Specification Part II. 
If the MAX15301 has latched off for a fault condition, sending the CLEAR_FAULTS command will cause 
a restart. 
VOUT_OV_FAULT_LIMIT 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x40 
Format: 
Unsigned integer mantissa 
Data Bytes: 
2 
Units: 
V 
Transfer: 
Read/Write Word 
Factory Value: 
0x0025 (see Description) 
Description/Notes: 
See Section 15.2 of the PMBus Specification Part II. 
VOUT_OV_FAULT_LIMIT mantissa data sent to and from the MAX15301 must be divided by 4096 to 
determine the actual voltage value, according to the fixed value of VOUT_MODE
. 
In the MAX15301, there are seven possible output voltage  ranges based on seven corresponding 
internal feedback divider taps. The MAX15301 hardware has 8-bit resolution for the overvoltage fault 
limit within each of these seven ranges. 
The desired value of VOUT_OV_FAULT_LIMIT is retained in memory, regardless of  limitations 
imposed by the feedback divider range and the 8-bit fault limit resolution, but the read-back value is 
based on actual hardware register settings. 
The factory value of 0x0025 (9mV) 
will be overridden during initialization to 
VOUT_COMMAND x 1.15, unless a specific value has been written to the User Store. 